Extended service
Service parameter(s) 45-55
32e
45 DHW charging deactivation time
Circuit Setting range Factory setting
I 0 ... 250 min. 0 min.
If the charging time has reached its maximum (line 44), the
charging is deactivated for the set time.
0: No deactivation time.
1 ... 250:
When the DHW charging time has reached
its maximum, DHW can only be charged
again when the deactivation time has
expired.
52 Compensation of heat loss in circulation circuit
Circuit Setting range Factory setting
I ON / OFF ON
Choose to compensate for the heat loss of the circulation circuit.
ON: The circulation circuit is kept warm by the
storage tank.
The motorized control valve (M1) is closed.
OFF: The circulation circuit is kept warm by the
heat exchanger.
The motorized control valve (M1) is active to
keep the charging temperature constant.
54 Activation / deactivation of DHW circulation pump
(P3) at anti-bacteria function
Circuit Setting range Factory setting
I ON / OFF OFF
At anti-bacteria function, the pump can be deactivated
independently of the schedule.
ON: The pump always operates according to
schedule II.
OFF: The pump is deactivated at anti-bacteria
function, independently of the schedule.
55 Activation / deactivation of DHW circulation pump
(P3) during DHW charging
Circuit Setting range Factory setting
I ON / OFF OFF
At DHW charging, the pump can be deactivated independently of
the schedule.
ON: The pump always operates according to
schedule II.
OFF: The pump is deactivated at DHW charging,
independently of the schedule.