10 Troubleshooting
Alarm
In the event of an error message try restarting the installation using the reset button on the control panel.
If restarting the heat pump does not help try rectifying the problem using the table below.
Message Meaning Cause Remedy
LOW PRESS
ERROR
Low pressure
error - The com-
pressor stops
and there is no
hot water pro-
duction.
Not enough anti-freeze in the
coolant system. Air in the brine
system. Blocked filter in the
brine system.
Fill the refrigerant with the correct
percentage of anti-freeze and bleed
using the safety valve on the volume
container. Check if the strainer needs
cleaning.
Coolant pump has stopped or
is running at slow speed.
Take temperature difference
readings between incoming and
outgoing coolant. The difference
should be between approximately
3-5°C.
Ice build up in the coolant
system.
Measure the amount of anti-freeze
in %, wait until the ice melts, which
affects the low pressure switch not
contacting the wiring.
Underfilled cooling system or
any leaks.
Drain and leak trace as well as filling
new refrigerant. No refilling of drai-
ned medium.
Blocked or filled drying filter in
the cooling circuit.
Measure the temperature difference
of the filter – max 2°C.
HIGH PRESS
ERROR
High pressure
error - The com-
pressor stops
and there is no
hot water pro-
duction.
Insufficiently opened radiator/
floor loop thermostats. Air in
the heating system. Blocked
strainer in the heating system,
located in the heat pump
return.
Open radiator / floor loop thermo-
stats. Fill and bleed the heating
system. Measure delta over the
heat pump supply and return lines.
Temperature difference.
Overfilled refrigerant circuit. Draining the refrigerant circuit and
refilling with new refrigerant, accor-
ding to the instructions.
Heat transfer fluid pump has
stopped or is running at slow
speed.
Check the heart transfer fluid pump.
MOTOR P
ERROR
Motor protec-
tion error - (Over
current relay
compressor or
brine pump).
The compressor
stops and there
is no hot water
production.
Phase drop or blown fuse. Check the fuses and cable terminals
(power supply to the compressor or
brine pump).
Poorly tightened electrical
connections.
Check the electrical connections.
Too low network voltage. Measure the voltage to the heat
pumps electrical connection.
Other alarms;
See separate manual for the control system.