525-690 V
Enclosure
type
Power [kW] Recommended
fuse size
Recommended
Max. fuse size
Recommended circuit
breaker (Moeller)
Max. trip level [A]
A3 1.1
1.5
2.2
3
4
5.5
7.5
gG-6
gG-6
gG-6
gG-10
gG-10
gG-16
gG-16
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
- -
B2/B4 11
15
18
22
gG-25 (11)
gG-32 (15)
gG-32 (18)
gG-40 (22)
gG-63 - -
B4/C2 30 gG-63 (30) gG-80 (30)
C2/C3 37
45
gG-63 (37)
gG-80 (45)
gG-100 (37)
gG-125 (45)
- -
C2 55
75
gG-100 (55)
gG-125 (75)
gG-160 (55-75) - -
Table 8.14 525-690 V, Enclosure Types A, B and C
8.8.2
UL Compliance
3x200-240 V
Recommended max. fuse
Power
[kW]
Bussmann
Type RK1
1)
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
1.1 KTN-R-10 JKS-10 JJN-10 FNQ-R-10 KTK-R-10 LP-CC-10
1.5 KTN-R-15 JKS-15 JJN-15 FNQ-R-15 KTK-R-15 LP-CC-15
2.2 KTN-R-20 JKS-20 JJN-20 FNQ-R-20 KTK-R-20 LP-CC-20
3.0 KTN-R-25 JKS-25 JJN-25 FNQ-R-25 KTK-R-25 LP-CC-25
3.7 KTN-R-30 JKS-30 JJN-30 FNQ-R-30 KTK-R-30 LP-CC-30
5.5 KTN-R-50 KS-50 JJN-50 - - -
7.5 KTN-R-60 JKS-60 JJN-60 - - -
11 KTN-R-80 JKS-80 JJN-80 - - -
15-18.5 KTN-R-125 JKS-125 JJN-125 - - -
22 KTN-R-150 JKS-150 JJN-150 - - -
30 KTN-R-200 JKS-200 JJN-200 - - -
37 KTN-R-250 JKS-250 JJN-250 - - -
Table 8.15 3x200-240 V, Enclosure Types A, B and C
Specifications
VLT
®
HVAC Drive Operating Instructions
58 MG11AJ02 - Rev. 2013-07-31
88