39MG.60.B1.02 - VLT is a registered Danfoss trademark
Introduction to
HVAC
LC filters 6002-6006, 200 - 240 V / 6002-6011 380 - 460 V
The drawing on the left gives the measurements of IP
20 LC filters for the above-mentioned power range.
Min. space above and under enclosure: 100 mm.
IP 20 LC filters have been designed for side-by-side
installation without any space between enclosures.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable
If EMC standards are to be complied with:
- EN 55011-1B: Max. 50 screened/armoured cable
Bookstyle: Max. 20 m screened/armoured cable
- EN 55011-1A: Max. 150 m screened/armoured cable
Weight: 175Z0825 7.5 kg
175Z0826 9.5 kg
175Z0832 9.5 kg
Installation of LC filter IP 20 Bookstyle
Installation of LC filter IP 20
LC filter
LC filter
VLT
VLT