A choice must thus be made by pressing [CHANGE
DATA] and choosing "Continue" + [OK] or "Stop" + [OK].
If parameters need to be changed, select
"Stop"; start up AMA all over.
WARNING 39
CHECK PAR. 104, 106
Parameters 104 Motor frequency f
M,N
, or 106 Rated
motor speed n
M,N
, have probably not been set correctly.
Check the setting and select "Continue" or [STOP].
WARNING 40
CHECK PAR. 103, 105
Parameter 103 Motor voltage, U
M,N
or 105 Motor
current, I
M,N
has not been set correctly. Correct
the setting and restart AMA.
WARNING 41
MOTOR TOO BIG (MOTOR TOO BIG)
The motor used is probably too big for AMA to be
carried out. The setting in parameter 102 Motor
power, P
M,N
may not match the motor. Check the
motor and choose ‘Continue or [STOP].
WARNING 42
MOTOR TOO SMALL (MOTOR TOO SMALL)
The motor used is probably too small for AMA to
be carried out. The setting in parameter 102 Motor
power, P
M,N
may not match the motor. Check the
motor and select "Continue" or [STOP].
ALARM 60
Safety stop (EXTERNAL FAULT)
Terminal 27 (parameter 304 Digital inputs) has been
programmed for a Safety interlock [3] and is a logic "0".
WARNING 61
Output frequency low (FOUT < FLOW)
The output frequency is lower than parameter 223
Warning: Low frequency, f
LOW
.
WARNING 62
Output frequency high (FOUT > FHIGH)
The output frequency is higher than parameter
224 Warning: High frequency, f
HIGH
.
WARNING/ALARM 63
Output current low (I MOTOR < I LOW)
The output current is lower than parameter 221
Warning: Low current, I
LOW
. Select the required
function in parameter 409 Function in case of no load.
WARNING 64
Output current high (I MOTOR > I HIGH)
The output current is higher than parameter 222
Warning: High current, I
HIGH
.
WARNIN G 65
Feedback low (FEEDBACK < FDB LOW)
The resulting feedback value is lower than parameter
227 Warning: Low feedback, FB
LOW
.
WARNIN G 66
Feedback high (FEEDBACK > FDB HIGH)
The resulting feedback value is higher than parameter
228 Warning: High feedback, FB
HIGH
.
WARNIN G 67
Remote reference low (REF. < REF LOW)
The remote reference is lower than parameter 225
Warning: Low reference, REF
LOW
.
WARNIN G 68
Remote reference high (REF. > REF HIGH)
The remote reference is higher than parameter 226
Warning:High reference, REF
HIGH
.
WARNIN G 69
Temperature auto derate (TEMP.AUTO DERATE)
The heat sink temperature has exceeded the maximum
value and the auto derating function (par. 411) is
active. Warning: Temp. Auto derate.
ALARM 75
Dry run (DRY RUN)
Dry run detection has been activated.
WARNIN G 99
Unknown fault (UNKNOWN ALARM)
An unknown fault has occurred that connot be
processed by the software.
Contact your Danfoss supplier.
MG.83.A2.02 - VLT is a registered Danfoss trademark