Data sheet ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys
15
VD.KT.W4.02 © Danfoss 04/2015
DEN-SMT/DK
Functions General functions:
The ECL Comfort 210 has all the required
functions of a modern electronic temperature
controller for heating and DHW applications.
The controller can be used as master or slave in
systems with master / slave ECL Comfort 210 /
310 controllers.
The ECL Application Key contains the application
software for exible conguration. Furthermore,
an update of the controller software is done
automatically, if required.
The ECL Comfort 210 contains, besides the
standard functions, log and alarm functions.
• The built-in Real Time Clock gives automatic
summer / winter time changeover, week and
holiday schedule.
Motor protection, which ensures stable control
and a long life of the motorized control valve, is
available for most of the applications. In periods
without heat demand, the motorized control
valve is exercised to avoid blocking.
Scheduled control (Comfort and Saving mode)
is based on a week program. A holiday program
gives the possibility to select days with comfort
or saving mode.
The ECL Comfort 210 can receive pulses from a
heat or ow meter to limit the power or the ow.
In many applications analog input (0 – 10 V) is
congured for pressure measuring among
others. The scaling is set in the controller.
Some applications are congured to handle
digital input. This function can be used to have
an external switch to run comfort or saving mode
or react on a ow switch signal.
• The control parameters, proportional band (Xp),
integration time (Tn), running time of the
motorized control valve and neutral zone (Nz)
can be set individually for each output (3-point
control).
Heating functions:
The heat curve (relationship between outdoor
temperature and desired ow temperature) is
set by means of 6 coordinate points or a slope
value. Max. / min. limitation of the desired ow
temperature can be set.
The return temperature limitation can work in
relation to the outdoor temperature or be a xed
value.
The heating cut-out function can switch OFF the
heating and stop the circulation pump at high
outdoor temperatures.
Based on the room temperature the ECL Comfort
210 can correct the desired ow temperature in
order to increase the comfort level.
The optimizer function ensures heating in the
desired periods (the lower outdoor temperature,
the earlier cut-in of the heating).
• The ramping function makes a smooth cut-in of
the heating valuable (district heating
installations).
The boost function makes a powerful cut-in of
the heating (boiler based installations).
• The circulation pump is controlled in relation to
heat demand and frost protection. In periods
without heat demand, the circulation pump is
exercised to avoid blocking.
The saving function gives two possibilities:
· reduced ow temperature with xed
reduction or reduction in relation to outdoor
temperature (the lower the outdoor
temperature, the less the reduction),
· heating o, still with active frost protection
DHW functions:
The Auto Tuning function with automatic setting
of control parameters for constant DHW
temperature is integrated in the application A217
and A266. However, Auto Tuning is only
applicable with valves that are approved for Auto
Tuning, i.e. the Danfoss types VB 2 and VM 2 with
split characteristic as well as logarithmic valves
such as VF and VFS.
The anti-bacteria function can follow a schedule
program.
The heating circuit can have sliding DHW priority.
Communication
The ECL Comfort 210 has an ECL 485 communication
bus, which is used for closed communication
between master, slave and RCUs.
Additionally, the ECL Comfort 210 has a non-
galvanically separated RS 485 bus for limited
Modbus communication. A USB connection (type
B) can be used for an ECL Tool.
Master / slave connections
Languages
Menu languages are selectable among approx. 20
languages. See “Language list.
Furthermore, English is always uploaded in parallel
to the selected language.