Danfoss C67 Betriebsanweisung Seite 13

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 84
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 12
Installation
10.5a Indirectly connected heating system with
or without mixing loop and secondarily
connected storage tank
System settings
Circuit Line Description Recomm.
setting
I 17 Influence on desired flow temp. 3
I 51
DHW charging pump /
changeover valve
ON
I 53
Desired flow temperature at
DHW charging
OFF
I 67
Adaptive function of S2 flow
temperature during DHW
charging
20
I 140
Function of temperature sensor
S5
2
I 152
Max limitation temperature at
sensor S2 during DHW charging
70*
* Line 152 = desired charging temperature
Heating circuit II can only be operated against heating circuit I.
This means that heating circuit II cannot be supplied if heating
circuit I is deactivated.
10h
Seitenansicht 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 83 84

Kommentare zu diesen Handbüchern

Keine Kommentare