VLT® 6000 HVACVLT® 8000 AQUAInstruction ManualCascade Controller Option

Seite 2

Cascade Controller OptionInstallation andWiring Instructions Installation and Wiring Instructions Installing the Cascade Controller Option CardThis

Seite 3

Cascade Controller Option 1. Access to Control Card Cassette• Remove Local Control Panel (LCP) keypad bypulling out from top by hand. LCP connectoron

Seite 4 - VLT 8000 AQUA

Cascade Controller OptionInstallation andWiring Instructions 3. Remove AFD Cassette and Ribbon Cables• Lift control board cassette from bottom.• Disc

Seite 5

Cascade Controller Option 5. Cascade Option Card Ribbon Cable Routing• Route ribbon cables from cascade controlleroption card through slot at side of

Seite 6 - Warning:

Cascade Controller Option 7. Connect Option Card Ribbon Cable toVLT Control B oard• Pull up collar (A) of control board ribbon cable socket.• DO NOT

Seite 7 - Operation modes

Cascade Controller Option 9. Install Chassis Ground Connections• Align ground strips over corresponding screwholes. (Strip with fewest contact points

Seite 8

Cascade Controller Option 12. Remove Wiring Clamp Mounting Fixture• Option card insulation pad is designed to use topmost cable wiring clamp screw ho

Seite 9

Cascade Controller Option Transmitter wiringPlease refer to chapter 10, Feedback Transmitter Wiring.MG.60.I5.22 - VLT is a registered Danfoss tradema

Seite 10 - Cascade Controller Option

Cascade Controller Option Standard casc ade control wiring diagramThe wiring diagram shows an example for astandard cascade control system with 4 fix

Seite 11

Cascade Controller Option Optional Hand/Off/Auto SwitchOptional Hand/Off/Auto SwitchIn standard cascade control mode, an optionalHand/Off/Auto switch

Seite 12

Cascade Controller Option ContentsSafety and precautions... 3Safety regu

Seite 13

Cascade Controller Option Lead Pump Alternation Wiring DiagramEvery pump must be fitted with a double powercontactor with a safety mechanical interlo

Seite 14

Cascade Controller Option Master drive in master/slave control wiring diagramThe wiring diagram below shows an example of aMaster drive in Master/Sla

Seite 15

Cascade Controller Option Slave drive in master/slave control wiring diagramEach slave drive is wired in the same way, receivingthe Start/Stop comman

Seite 16

Cascade Controller Option Changed Drive functions IntroductionInstallation of the Cascade Controller Option cardinto the AFD overrides some existing

Seite 17

Cascade Controller OptionChanged Drivefunctions Changed systemstop functionsTwo stop functions are provided by the cascadecontroller option. One func

Seite 18

Cascade Controller Option User Interface How to use the LCP for programmingThe combined display and keypad on the front of theAFD is called the Loca

Seite 19

Cascade Controller OptionUserInterface• Reversing• Setup select lsb - Setup select msb• Jog• Run permissive• Lock for data change• Stop command from s

Seite 20

Cascade Controller OptionData Item: Unit:Resulting reference, % [%]Resulting reference, unit [unit]Frequency [Hz]% of maximum outputfrequency[%]Motor

Seite 21

Cascade Controller OptionThis display mode shows three operating data valuesin the top line programmed via parameters 007,008, and 009. Pressing the [

Seite 22

Cascade Controller Option Parameter setting procedureEnter or change parameter data or settings as follows:1. Press [Quick Menu] or [Extended Menu] k

Seite 23 - Changed Drive functions

Cascade Controller OptionInitial Setup ... 40

Seite 24

Cascade Controller OptionAFD and CascadeController Setup AFD and Cascade Controller Setup IntroductionA new quick menu list is activated when a casc

Seite 25 - User Interface

Cascade Controller Option Quick Menu SummaryQuick MenunumberParame-ter num-berName Units Range Factory settingBasic Drive Set Up parameters001 001 La

Seite 26

Cascade Controller Option LanguageQuick Menu 001 Par. 001 Languag e(LANGUAGE)Value:✭English (ENGLISH)German (DEUTSCH)French (FRANCAIS)Danish (DANSK)S

Seite 27

Cascade Controller OptionDescription of choice:Select a value that equals the nameplate data on themotor, regardless of the AC input voltage of the AF

Seite 28

Cascade Controller OptionQuick Menu 009 Par. 206 Ramp-up time(RAMP U P TIME)Value:1 - 3600 sec.✭ Depends on unitFunction:The ramp-up time is the accel

Seite 29

Cascade Controller Optionis a fault condition or when the drive looses power.Terminal wires 1 and 3 are wired together.Alarm is selected when a loss o

Seite 30

Cascade Controller OptionDescription of choice:Setthevaluetobeshownonthedisplaywhenthefeedback signal is at its minimum value.Quick Menu 015 Par. 414

Seite 31

Cascade Controller OptionQuick Menu 019 Par. 205 Maximum reference(MAX. REFERENCE)Value:Par. 204 RefMIN- par. 414 Maximum feedback✭ 50.000 HzFunction:

Seite 32

Cascade Controller Option Alternate programmingSetup configuration and copying parametersThe AFD has four parameter setups that can beprogrammed. Eac

Seite 33

Cascade Controller OptionExtended Menu Par. 004 LCP Copy(LCP COPY)Value:✭No copying (NO COPY)[0]Upload all parameters(UPLOAD ALL PARAMET.)[1]Download

Seite 34

Cascade Controller OptionSafety andprecautions Safety and precautions175ZA677.12Cascade Controller OptionforVLT 6000 HVACandVLT 8000 AQUAOperating In

Seite 35

Cascade Controller OptionStandard CascadeController Setup Standard Cascade Controller Setup IntroductionIn standard cascade control, an AFD with the

Seite 36

Cascade Controller Option Initial SetupInstructions for programming Quick Menu items1-20 are presented in Chapter 5, AFD andCascade Controller Card S

Seite 37

Cascade Controller OptionQuick Menu 022 Par. 713 Staging Bandwidth %(STAGING BANDW%)Value:1 - 100%✭ 10%Function:In cascade control systems, to avoid f

Seite 38

Cascade Controller OptionDescription of choice:Set the staging on time delay. A delay timeof 30 seconds (factory setting) is sufficient inmost systems

Seite 39

Cascade Controller OptionCommissioning the Cascade ControllerTo avoid unintended staging during the commissioningphase and fine tuning of the controll

Seite 40

Cascade Controller Optionsystem. Ensure that the staging frequency settingallows the check valve to remain open.Quick Menu 028 Par. 741 Destaging freq

Seite 41

Cascade Controller OptionQuick Menu 029 Par. 418 Setpoint 1(SETPOINT 1)Value:Feedback Min. to Feedback Max✭ 0.000Function:The default feedback process

Seite 42

Cascade Controller OptionDescription of choice:Set the desired feedback maximum within theprogrammed minimum and maximum in Quick Menuitems 014 and 01

Seite 43

Cascade Controller Option Programming of the Lead Pump Alter-nation FunctionThe standard cascade controller parameters and thefollowing parameters 75

Seite 44

Cascade Controller OptionDescription of choice:Select which pump you want to be the lead pump.Quick Menu 039 Par. 753 AlternationRestart Delay(ALT. RE

Seite 45

Cascade Controller OptionThe voltage of the AFD is dangerouswhenever the equipment is connectedto mains. Incorrect installation of themotor or the fre

Seite 46

Cascade Controller Option Alternate programmingIn water supply systems, it is often impractical toplaceapressuresensoratthefarendofthesystem.In HVAC

Seite 47

Cascade Controller Option Master/Slave Cascade Control Setup IntroductionIn Master/Slave cascade control operation, the AFDwith the cascade control

Seite 48

Cascade Controller OptionMaster/Slave CascadeControl Setup Initial SetupInstructions for programming Quick Menu items1-20 are presented in Chapter 5,

Seite 49

Cascade Controller OptionThe range is determined by Quick Menu item 14(parameter 413, Minimum Feedback)andQuickMenuitem 15 (parameter 414, Maximum Fee

Seite 50

Cascade Controller Optionthere are three types of output signals: 0 to 20 mA, 4to 20 mA, or 0 to 32000 pulses. The pulse rate is setby parameter 320,

Seite 51

Cascade Controller OptionDescription of choice:Select the PID controller response option.MG.60.I5.22 - VLT is a registered Danfoss trademark54

Seite 52

Cascade Controller Option Step 2: Slave Drive ProgrammingThe slave drives run in open loop mode and recievestop/start and speed reference commands fr

Seite 53

Cascade Controller Optionthe drive’s PID controller to respond to system changesas programmed. Pumps or fans are staged on andoff in response to the s

Seite 54

Cascade Controller OptionSystemOptimization System Optimization System start up and final adjustmentsAfter Master drive and slave programming iscomp

Seite 55

Cascade Controller Option Optimization of the process regulatorQuick Menu 043 Par. 423 PID proportional gain(PID PROP. GAIN)Value:0.00 - 10.00✭ 0.30F

Seite 56

Cascade Controller Option175ZA678.13Warning:Touching the electrical parts may be fatal - even after the equipment hasbeen disconnected from mains.6002

Seite 57

Cascade Controller OptionFeedback TransmitterWiring Feedback Transmitter Wiring Connecting feedback transmittersTerminal 12 and 13 of the AFD provid

Seite 58 - System Optimization

Cascade Controller OptionProgramming:Parameter Parameter ParameterNumber Description Value415 Ref./FDBK UNIT Process unit413 MIN. FEEDBACK Transmitter

Seite 59

Cascade Controller OptionMaximum is selected, the feedbacks will be equalto or less than their associated setpoints.Feedback 1 is associated with Setp

Seite 60 - Feedback Transmitter Wiring

Cascade Controller Option Parameter group 700 definitionsPara Name Description Unit Range FactorySettingChangeDuringOperationData Type ConversionInde

Seite 61

Cascade Controller OptionParameter group 700,all parametersConversion Index FactorsConversion Index Conversion Factor74 3.62 100.0110.001.0-1 0.1-2 0.

Seite 62

Cascade Controller Option Service parameters Display informationParameters 724 through 738 provide operationalinformation including the number of ho

Seite 63

Cascade Controller OptionServiceparameters Relay statusThe display panel on the AFD allows readingthe status of the relays.Press the [DISPLAY MODE] k

Seite 64

Cascade Controller Option IndexLLead Pump Alternation... 39MG.60.I5.22 - VLT is a registered Danfoss

Seite 65 - Service parameters

Rev. 2006-01-11www.danfoss.com/drives175R0240 MG60I522*MG60I522*

Seite 66 - 10010100

Cascade Controller Option Operation modes Cascade Control OperationWith the cascade controller option card, the AFD(Adjustable Frequency Drive) can

Seite 67

Cascade Controller OptionOperationmodes Standard Cascade Control ModeIn standard cascade control, the AFD with the CascadeController option card inst

Seite 68 - *MG60I522*

Cascade Controller Option Master/Slave C ascade Control ModeMaster/slave systems control multiple pumps inparallel at the same output frequency. Pump