Datasheet TP5000 Si Programmable Room Thermostat
Part No. 082v07 04/09
Installer Advanced
Programming Settings
Option Description Factory Setting Other Setting
User Advanced Programming Options Use + or - key to scroll between options, use Λ or V keys to select option setting
1 Enable/disable A/B block programming 0 Disabled 1 Enabled
3 Automatic summer/winter time change 2 European rules
0 Disabled
1 Manual time change
3 USA rules, post 2006
4 USA rules. pre-2007
4
Time zone off set - UST models 00:00 Use UST clock setting ± 12 Hours off set from UST
Time zone off set - CET models 00:00 Use CET clock setting ± 12 Hours off set from CET
10 Set frost protection default temperature 5 5°C 5-30°C
11 Start-up type 0 Fixed time start-up
1 Optimum start control
2 Delayed start-up
12
Optimum start control setting, maximum
pre-heat period based upon 2°C deviation
from next event temperature.
(Only accessible if option 11 is set to 2)
1:00 60 minutes
0:15 15 minutes
0:30 30 minutes
0:45 45 minutes
1:15 75 minutes
1:30 90 minutes
1:45 105 minutes
2:00 120 minutes
13
OSC or delay start function active
(Only accessible if option 11 is set to 1 or 2)
0 First event of day only 1 All events
Option Description Factory Setting Other Setting
Installer Advanced Programming Options Use + or - key to scroll between options, use Λ or V keys to select option setting
30 Set range upper limit 30°C 40-50°C
31 Set range lower limit 5°C 5-40°C
32 Enable/disable Off function at lower limit 0 Enabled 1 Disabled
33 Enable/disable On function at upper limit 0 Disabled 1 Enabled
34 Set chrono-proportional cycle rate 6 6 cycles per hour
3 3 cycles per hour
9 9 cycles per hour
12 12 cycles per hour
35 Set integration time 2.5 2.50%
55%
10 10%
36 Set temperature override limit 0 No limit
1 Limited to ±2°C
2 Disabled, no override
37 Set time duration of override 0 Next event
1 1 hour
2 2 hours
3 3 hours
4 4 hours
38 Relay park status on battery low volt detect 0 Relay parked O 1 Relay parked On
40 Number of Events 6 6 Switching events per day
1 Thermostat mode
2 2 Switching events per day
4 4 Switching events per day
41 Operating Mode 5-2 5/2 day programming 24 24 Hour programming
70 Keyboard lock type 0 Normal Lock 1 Full lock
71
Random time on start-up (not battery
models)
0 Disabled 1 Enabled
72 Site ID number (user defi ned) 00 01 to 99
73 Thermostat ID number (user defi ned) 00 001 to 999
74 Date format for calendar clock 0 European (dd/mm/yy) 1 North American (mm/dd/yy)
81 Thermostat calibration bias 0 ±1.5K
90
Remote sensor confi guration
(A models only)
0 0, Disabled
1 Room/duct
2 Limit, (fl oor)
3 Start-up (digital input)
93
Limit sensor set point adjustment
(Only accessible if Option 90 is set to 2)
27°C 20-50°C
94
Start-up (digital input) NO or NC
(Only accessible if Option 90 is set to 3)
0
NC, open circuit to change
to thermostat mode
1
NO, close circuit to change to
thermostat mode
Installer Hardware Settings
(Switches show factory setting)
1
2
Keyboard enabled
Reset disabled Reset enabled
Keyboard disabled
OFF
ON
Sw. No.