Motor Set-up
The Quick Menu Motor Set-up guides through the needed
motor parameters.
No & Name Range Default Function
0-03 Regional
Settings
[0] Interna-
tional
[1] US
0
0-06 Grid
Type
[0]-[132] please
see start-up
wizard for
open loop
application
Size selected Select operating
mode for restart
upon
reconnection of
the frequency
converter to
mains voltage
after power
down
1-20 Motor
power
0.12-110 kW/
0.16-150 Hp
Size related Enter motor
power from
nameplate data
1-22 Motor
Voltage
50.0 - 1000.0 V Size related Enter motor
voltage from
nameplate data
1-23 Motor
Frequency
20.0 - 400.0 Hz Size related Enter motor
frequency from
nameplate data
1-24 Motor
Current
0.01 - 10000.00
A
Size related Enter motor
current from
nameplate data
1-25 Motor
Nominal
Speed
100.0 - 9999.0
RPM
Size related Enter motor
nominal speed
from nameplate
data
4-12 Motor
Speed Low
Limit [Hz]
0.0 - 400 Hz 0.0 Hz Enter the
minimum limit
for low speed
4-14 Motor
Speed High
Limit [Hz]
0-400 Hz 65 Enter the
maximum limit
for high speed
3-41 Ramp 1
Ramp up Time
0.05 - 3600.0 s Size related Ramp up time
from 0 to rated
motor frequency
1-23 Motor
Frequency
3-42 Ramp 1
Ramp Down
Time
0.05 - 3600.0 s Size related Ramp down time
from rated motor
frequency
1-23 Motor
Frequency to 0
1-73 Flying
Start
[0] Disabled
[1] Enabled
0 Select Enable to
enable the
frequency
converter to
catch a spinning
motor
Changes Made
Changes Made lists all parameters changed since factory
setting. Only the changed parameters in current edit-setup
are listed in changes made.
If the parameters value is changed back to factory setting's
value from another different value, the parameter will NOT
be listed in Changes Made.
1. Press [Menu] key to enter the Quick Menu until
indicator in display is placed above Quick Menu.
2.
Press [
] [
] to select either FC101 wizard, closed
loop setup, motor setup or changes made, then
press [OK].
3.
Press [
] [
] to browse through the parameters
in the Quick Menu.
4. Press [OK] to select a parameter.
5.
Press [
] [
] to change the value of a parameter
setting.
6. Press [OK] to accept the change.
7. Press either [Back] twice to enter “Status”, or
press [Menu] once to enter “Main Menu”.
The Main Menu accesses all parameters.
1. Press [Menu] key until indicator in display is
placed above “Main Menu”.
2.
Use [
] [
] to browse through the parameter
groups.
3. Press [OK] to select a parameter group.
4.
Use [
] [
] to browse through the parameters in
the specific group.
5. Press [OK] to select the parameter.
6.
Use [
] [
] to set/change the parameter value.
Quick Guide VLT HVAC Basic Drive Quick Guide
MG18A302 - VLT
®
is a registered Danfoss trademark 27
1 1