10 Manual RS8DY302 © Danfoss 07-2005 EKC 102
Copy from the programming key
This function downloads a set of settings earlier saved in
the controller. Select the relevant number.
When copying has started the display returns to o66.
After two seconds you can move back into the mennu
again and check whether the copying was satisfactory.
Showing of a negative figure spells problems. See the
significance in the Fault Message section.
o66
Save as factory setting
With this setting you save the controller’s actual settings
as a new basic setting (the earlier factory settings are
overwritten).
o67
Extra sensor
Here you define the application for the Saux sensor.
0: None, no sensor is connected
1: Product sensor
2: Condenser temperature sensor with alarm function
o69
S5 sensor
Here you define the application for the S5 sensor.
0: Defrost sensor
1: Product sensor
o70
Relay 2
Here you define the application for relay 2
EKC 102B: 1=compressor. 2=alarm
EKC 102C: 1=defrost. 2=alarm
o71
Service
Temperature measured with Saux sensor
u03
Temperature measured with S5 sensor
u09
Status on DI1 input. on/1=closed
u10
Status on relay for refrigeration
u58
Status on relay 2 (refrigeration, alarm or defrost)
u70
Fault message
In an error situation the LED’s on the front will flash and the
alarm relay will be activated. If you push the top button in this
situation you can see the alarm report in the display. If there are
several, you can continue pushing to see them.
There are two kinds of error reports - it can either be an alarm
occurring during the daily operation, or there may be a defect in
the installation.
A-alarms will not become visible until the set time delay has
expired.
E-alarms, on the other hand, will become visible the moment the
error occurs.
(An A alarm will not be visible as long as there is an active E
alarm).
Here are the messages that may appear:
A1: High temperature alarm
A2: Low temperature alarm
A4: Door alarm
AA45: Standby position (stopped refrigeration via r12 or DI
input)
A61: Condenser temperature alarm
E1: Faults in the controller
E27: Sensor error on S5
E29: Sensor error on Sair
E30: Sensor error on Saux
When copying settings to or from a copying key with functions
o65 or o66, the following information may appear:
0: Copying concluded and OK
4: Copying key not correctly mounted
5: Copying was not correct. Repeat copying
6: Copying to EKC incorrect. Repeat copying
7: Copying to copying key incorrect. Repeat copying
8: Copying not possible. Order number or SW version do not
match
9: Communication error and timeout
10: Copying still going on
(The information can be found in o65 or o66 a couple of seconds
after copying has been started).
Operating status
The controller goes through some regulating situations where it
is just waiting for the next point of the regulation. To make these
“why is nothing happening” situations visible, you can see an
operating status on the display. Push briefly (1s) the upper but
-
ton. If there is a status code, it will be shown on the display. The
individual status codes have the following meanings:
S0: Regulating
S2: When the compressor is operating it must run for at least x
minutes.
S3: When the compressor is stopped, it must remain stopped for at
least x minutes.
S10: Refrigeration stopped by main switch. Either with r12 or a
DI-input
S11: Refrigeration stopped by thermostat
S14: Defrost sequence. Defrost in progress
S17: Door is open. DI input is open
S20: Emergency cooling
S25: Manual control of outputs
S32: Delay on outputs during start-up
Other displays:
non: The defrost temperature cannot be displayed. There is no
sensor
-d-: Defrost in progress. /First cooling after defrost
PS: Password required. Set password