4 Manual RS8DY302 © Danfoss 07-2005 EKC 102
Start of defrost
A defrost can be started in different ways
Interval: Defrost is started at fixed time intervals, say, every
eighth hour
Refrigeration time:
Defrost is started at fixed refrigeration time inter
vals, in other words, a low need for
refrigeration will ”postpone the coming defrost
Contact Defrost is started here with a pulse signal on a
digital input.
Manual: An extra defrost can be activated from the control-
lers lower-most button
S5-temp. In 1:1 systems the efficiency of the evaporator can
be followed. Icing-up will start a defrost.
Start-up After a power cut the system can be started with a
defrost.
All the mentioned methods can be used at random – if just one
them is activated a defrost will be started. When the defrost starts
the defrost timers are set at zero
.
Refrigeration control with two compressors
The two compressors must be of the same size.
When the controller demands refrigeration it will first cut in the
compressor with the shortest operating time. After the time delay
the second compressor will be cut in.
When the temperature has dropped to ”the middle of the differen
-
tial” the compressor with the longest operating time will be cut
out.
If the Compressor in operation is unable to lower the temperature
to the cutout point, the other compressor will be cut in again. This
happens when the temperature reaches the upper part of the
differential. If the temperature, on the contrary, remains ”stuck
within the differential for two hours there will be a change-over
between the two compressors so that the operating time can be
equalised.
The compressors used must be of a type that is capable of starting
up against a high pressure.
Digital input
2 of the controllers has a digital input which can be used for the
following functions:
- Door contact function with alarm if the door has been open for
too long.
- Defrost start
- Start/stop of regulation
- Change-over to night operation
A pulse signal