Danfoss VLT 8000 AQUA Installationsanleitung Seite 39

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 41
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 38
VL 8000 AQUA
Installation
Infinitely variable change of numeric data value
If the chosen parameter represents a numeric data
value, a digit is first selected by means of the [<>] keys.
175ZA699.10
SETUP
1
50.0 Hz
FREQUENCY
209 JOG FREQUENCY
0
9 .0 Hz
SETUP
1
Then the chosen digit is changed infinitely by
means of the [+/-] keys:
175ZA700.10
SETUP
1
50.0
FREQUENCY
209 JOG FREQUENCY
1
0.0 Hz
SETUP
1
The chosen digit flashes. The bottom display
line shows the data value that will be entered
(saved) when signing off with [OK].
Changing of data value, step-by-step
Certain parameters can be changed both step by
step and infinitely variably. This applies to Motor
power (parameter 102), Motor voltage (parameter
103) and Motor frequency (parameter 104).
This means that the parameters are changed
bothasagroupofnumericdatavaluesandas
numeric data values infinitely variably.
Manual initialization
Disconnect from line and hold the [DISPLAY MODE] +
[CHANGE DATA] + [OK] keys down while at the same
time reconnecting the line supply. Release the keys; the
AFD has now been programmed for the factory setting.
The following parameters are not zeroed by means of manual
initialization:
Parameter 500, Protocol
600, Operating hours
601, hours run
602, kWh counter
603, Nu mber of powe r-ups
604, Numbe r of overtemperatures
605, Num ber of over voltages
It is also possible to carry out initialization via
parameter 620 Operating mode.
MG.80.A6.22 - VLT is a registered Danfoss trademark
85
Seitenansicht 38
1 2 ... 34 35 36 37 38 39 40 41

Kommentare zu diesen Handbüchern