User Guide DLX Series L00410623-1 27
Negative Grounded PV String
Figure 4.3.10: Negative grounded PV string
The inverter is delivered from the
factory in an ungrounded PV string
configuration as standard.
Connect the grounding strap between
N5 (fig. 4.3.9) and the DC ground
receptacle labeled GND/PE in the
inverter lower compartment.
Positive Grounded PV String
Figure 4.3.11: Positive grounded PV string
Connect the positive conductors (+)
to the terminals labeled 2.Grounded,
and the negative conductors (-) to
the terminals labeled 1.Ungrounded.
Switch the conductors connected to
N4 and P4 (fig. 4.3.9).
Connect the grounding strap between
N5 (fig. 4.3.9) and the DC ground
receptacle labeled GND/PE in inverter
lower compartment.
4.3.4.4. Connection Procedures
The DC conductors connecting the PV array to the inverter must each have a minimum
rating of 600 V
DC
at any operating temperatures.
The DC conductor cables must be sized for correct temperature rating and sunlight
resistance. Use copper wire with a cross-section area of between 6 mm
2
to16 mm
2
/ 10
AWG to 6 AWG and temperature rating 90° C /194° F for all connections. Ensure
compliance with the relevant national electrical regulations!