User Guide DLX Series L00410623-1 59
6.2.4.4. Plant Setup
Plant Setup displays useful information about the PV plant, which can be changed using
the Owner password.
Company/Customer Name
The customer / owner name
Site
The site name
Installation Date
May be used for setting the install date
Service Date
May be used for setting the most recent service date
Responsible
Field for keeping a note of the company/person responsible for service
Unit Name
This text string is displayed in the master unit’s list of connected inverters
Message
An extra message field for additional notes
Plant Apparent Power
The product of voltage and current from the entire PV plant [kVA]
6.2.4.5. Grid Setup
Grid Setup displays grid settings based on the selected country. The settings can be
changed within 5 hours after Start Up using the Owner password. Thereafter it is only
accessible by using the Installer password, which may only be obtained by the installer
contacting Danfoss.
Up or Down – Navigate through the submenus
Enter – Select submenu/confirm
General Grid Setup
General Grid Setup displays grid parameters related to the selected grid standard.
Country
Grid code of installation
Country code
Name of the grid protection standard
Grid nom voltage
Nominal voltage of the grid on site
Grid nom frequenc
Nominal frequency of the grid on site
Feeding phase
The phase the inverter is connected to:
TN/TT: Not set, L1, L2, L3
IT: Not set, L1-L2, L1-L3, L2-L3
Voltage limit min
Lower disconnection limit of the grid voltage on site
Voltage limit max
Upper disconnection limit of the grid voltage on site
Voltage time limits min
Minimum disconnection time limit
Voltage time limits max
Maximum disconnection time limit
Frequency limits min
Lower disconnection limit of the grid frequency on site
Frequency limits max
Upper disconnection limit of the grid frequency on site
Frequency time limits min
Minimum disconnection time limit
Frequency time limits max
Maximum disconnection time limit
AC volt avg turnoff
Limits for disconnection based on an average voltage over a certain time
period. eg. average voltage of >253Vac over 10 minutes