General technical data
Cable lengths and cross-sections:
Max. motor cable length, screened cable ..................................................................................................... 150 m
Max. motor cable length, unscreened cable ................................................................................................. 300 m
Max. motor cable length, screened cable VLT 6011 380-460 V .................................................................... 100 m
Max. DC-bus cable length, screened cable ........................................... 25 m from frequency converter to DC bar.
Max. cable cross-section to motor, see next section
Max. cross-section for control cables ..........................................................................................1.5 mm
2
/16 AWG
Max. cross-section for serial communication ...............................................................................1.5 mm
2
/16 AWG
Control characteristics:
Frequency range ................................................................................................................................... 0 - 1000 Hz
Resolution on output frequency .............................................................................................................. ±0.003 Hz
System response time ................................................................................................................................ 3 msec.
Speed, control range (open loop)...................................................................................... 1:100 of synchro. speed
Speed, control range (closed loop) ................................................................................. 1:1000 of synchro. speed
Speed, accuracy (open loop) ............................................................................ < 1500 rpm: max. error ± 7.5 rpm
> 1500 rpm: max. error of 0.5% of actual speed
Process, accuracy (closed loop) ........................................................................ < 1500 rpm: max. error ± 1.5 rpm
> 1500 rpm: max. error of 0.1% of actual speed
All control characteristics are based on a 4-pole asynchronous motor
Accuracy of Display readout (parameters 009-012 Display readout):
Motor current [5], 0 - 140% load ............................................................ Max. error: ±2.0% of rated output current
Power kW [6], Power HP [7], 0 - 90% load .............................................. Max. error: ±5.0% of rated output power
Externals:
Enclosure.................................................................................................................................... IP 00, IP 20, IP 54
Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ............................................................. 93 % +2 %, -3 % (IEC 68-2-3) for storage/transport
Max. relative humidity ................................................ 95% non condensing (IEC 721-3-3; class 3K3) for operation
Ambient temperature ..............................................................................................................................................
VLT 6002-6005 200-240V, 6002-6011 380-460V, Bookstyle, IP20 ...............Max. 45°C (24-hour average max. 40°C)
VLT 6006-6062 200-240V, 6016-6275 380-460V, IP00, IP20 .......................Max. 40°C (24-hour average max. 35°C)
VLT 6002-6062 200-240V, 6002-6275 380-460V, IP54 .................................Max. 40°C (24-hour average max. 35°C)
Min. ambient temperature in full operation ........................................................................................................ 0°C
Min. ambient temperature at reduced performance ....................................................................................... -10°C
Temperature during storage/transport ............................................................................................. -25 - +65/70°C
Max. altitude above sea level ...................................................................................................................... 1000 m
EMC standards applied, Emission ........................................... EN 50081-1/2, EN 61800-3, EN 55011, EN 55014
Immunity .............................. EN 50082-2, EN 61000-4-2, IEC 1000-4-3, EN 61000-4-4
EN 61000-4-5, ENV 50204, EN 61000-4-6, VDE 0160/1990.12
VLT 6000 HVAC protection:
Electronic motor thermal protection against overload.
Temperature monitoring of heat-sink ensures that the VLT frequency converter cuts out if the temperature
reaches 90°C for IP 00 and IP 20. For IP 54, the cut-out temperature is 80°C. An overtemperature can only
be reset when the temperature of the heat-sink has fallen below 60°C.
The VLT frequency converter is protected against short-circuiting on motor terminals U, V, W.
The VLT frequency converter is protected against earth fault on motor terminals U, V, W.
Monitoring of the intermediate circuit voltage ensures that the VLT frequency converter cuts out if the
intermediate circuit voltage gets too high or too low.
If a motor phase is missing, the VLT frequency converter cuts out.
If there is a mains fault, the VLT frequency converter is able to carry out a controlled deramping.
If a mains phase is missing, the VLT frequency converter will cut out when a load is placed on the motor.