VLT
®
6000 HVAC
17MD.60.A2.02 - VLT is a registered Danfoss trade mark
■■
■■
■ General technical data
Cable lengths and cross-sections:
Max. motor cable length, screened cable ..................................................................................................... 150 m
Max. motor cable length, unscreened cable ................................................................................................. 300 m
Max. motor cable length, screened cable VLT 6011 380-460 V .................................................................... 100 m
Max. DC-bus cable length, screened cable ........................................... 25 m from frequency converter to DC bar.
Max. cable cross-section to motor, see next section
Max. cross-section for control cables ..........................................................................................1.5 mm
2
/16 AWG
Max. cross-section for serial communication ...............................................................................1.5 mm
2
/16 AWG
Control characteristics:
Frequency range ................................................................................................................................... 0 - 1000 Hz
Resolution on output frequency .............................................................................................................. ±0.003 Hz
System response time ................................................................................................................................ 3 msec.
Speed, control range (open loop)...................................................................................... 1:100 of synchro. speed
Speed, control range (closed loop) ................................................................................. 1:1000 of synchro. speed
Speed, accuracy (open loop) ............................................................................ < 1500 rpm: max. error ± 7.5 rpm
> 1500 rpm: max. error of 0.5% of actual speed
Process, accuracy (closed loop) ........................................................................ < 1500 rpm: max. error ± 1.5 rpm
> 1500 rpm: max. error of 0.1% of actual speed
All control characteristics are based on a 4-pole asynchronous motor
Accuracy of Display readout (parameters 009-012 Display readout):
Motor current [5], 0 - 140% load ............................................................ Max. error: ±2.0% of rated output current
Power kW [6], Power HP [7], 0 - 90% load .............................................. Max. error: ±5.0% of rated output power
Externals:
Enclosure.................................................................................................................................... IP 00, IP 20, IP 54
Vibration test .................................. 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ............................................................. 93 % +2 %, -3 % (IEC 68-2-3) for storage/transport
Max. relative humidity ................................................ 95% non condensing (IEC 721-3-3; class 3K3) for operation
Ambient temperature ..............................................................................................................................................
VLT 6002-6005 200-240V, 6002-6011 380-460V, Bookstyle, IP20 ...............Max. 45°C (24-hour average max. 40°C)
VLT 6006-6062 200-240V, 6016-6275 380-460V, IP00, IP20 .......................Max. 40°C (24-hour average max. 35°C)
VLT 6002-6062 200-240V, 6002-6275 380-460V, IP54 .................................Max. 40°C (24-hour average max. 35°C)
Min. ambient temperature in full operation ........................................................................................................ 0°C
Min. ambient temperature at reduced performance ....................................................................................... -10°C
Temperature during storage/transport ............................................................................................. -25 - +65/70°C
Max. altitude above sea level ...................................................................................................................... 1000 m
EMC standards applied, Emission ........................................... EN 50081-1/2, EN 61800-3, EN 55011, EN 55014
Immunity .............................. EN 50082-2, EN 61000-4-2, IEC 1000-4-3, EN 61000-4-4
EN 61000-4-5, ENV 50204, EN 61000-4-6, VDE 0160/1990.12
VLT 6000 HVAC protection:
••
••
• Electronic motor thermal protection against overload.
••
••
• Temperature monitoring of heat-sink ensures that the VLT frequency converter cuts out if the temperature
reaches 90°C for IP 00 and IP 20. For IP 54, the cut-out temperature is 80°C. An overtemperature can only
be reset when the temperature of the heat-sink has fallen below 60°C.
••
••
• The VLT frequency converter is protected against short-circuiting on motor terminals U, V, W.
••
••
• The VLT frequency converter is protected against earth fault on motor terminals U, V, W.
••
••
• Monitoring of the intermediate circuit voltage ensures that the VLT frequency converter cuts out if the
intermediate circuit voltage gets too high or too low.
••
••
• If a motor phase is missing, the VLT frequency converter cuts out.
••
••
• If there is a mains fault, the VLT frequency converter is able to carry out a controlled deramping.
••
••
• If a mains phase is missing, the VLT frequency converter will cut out when a load is placed on the motor.