VLT
®
6000 HVAC
18
MD.60.A2.02 - VLT is a registered Danfoss trade mark
Mains supply 3 x 200 - 240 V
According to international requirements
VLVL
VLVL
VL
T typeT type
T typeT type
T type
60026002
60026002
6002
60036003
60036003
6003
60046004
60046004
6004
60056005
60056005
6005
60066006
60066006
6006
60086008
60086008
6008
60116011
60116011
6011
Output current
4 )
I
VLT,N
[A] 6.6 7.5 10.6 12.5 16.7 24.2 30.8
I
VLT, MAX
(60 s) [A] 7.3 8.3 11.7 13.8 18.4 26.6 33.9
Output (240 V) S
VLT,N
[kVA] 2.7 3.1 4.4 5.2 6.9 10.1 12.8
Typical shaft output P
VLT,N
[kW] 1.1 1.5 2.2 3.0 4.0 5.5 7.5
Typical shaft output P
VLT,N
[HP] 1.5 2 3 4 5 7.5 10
Max. cable cross-section
to motor and DC-bus [mm
2
/AWG] 4/10 4/10 4/10 4/10 4/10 16/6 16/6
Max. input current (200 V) (RMS) I
L,N
[A] 6.0 7.0 10.0 12.0 16.0 23.0 30.0
Max. cable cross-section
power [mm
2
]/[AWG]
2 )
4/10 4/10 4/10 4/10 4/10 16/6 16/6
Max. pre-fuses [A]/UL
1 )
[A] 16/10 16/15 25/20 25/25 35/30 50 60
Mains contactor [Danfoss type] CI 6 CI 9 CI 12 CI 12 CI 6 CI 9 CI 16
[AC value] AC-3 AC-3 AC-3 AC-3 AC-1 AC-1 AC-1
Efficiency
3)
0.95
Weight IP 20 [kg] 7 7 9 9 23 23 23
Weight IP 54 [kg] 11.5 11.5 13.5 13.5 35 35 38
Power loss at max. load. [W] Total 76 95 126 172 194 426 545
Enclosure VLT type Bookstyle IP 20/Compact IP 20/IP 54
(Bookstyle IP 20 is available in power range VLT 6002-6005).
1. If UL/cUL is to be complied with, pre-fuses type Bussmann KTN-R, FWH and FWX or similar must be used. Pre-fuses type gG
must be used for VLT 6002 - VLT 6032, 200/240 V and VLT 6002 - VLT 6062, 380/460 V. Pre-fuses type gR must be used for
VLT 6042 - 6062, 200/240 V and VLT 6075 - VLT 6275, 380/460 V. Fuses must be designed for protection in a circuit capable of
supplying a maximum of 100,000 Amps ms (symmetrical), 500 V maximum.
2. American Wire Gauge.
3. Measured using 30 m screened motor cable at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V
5. Connection stud 1 x M8 / 2 x M8.
Mains supply 3 x 200 - 240 V
According to international requirements
VLVL
VLVL
VL
T typeT type
T typeT type
T type
60166016
60166016
6016
60226022
60226022
6022
60276027
60276027
6027
60326032
60326032
6032
60426042
60426042
6042
60526052
60526052
6052
60626062
60626062
6062
Output current I
VLT,N
[A] (200-230 V) 46.2 59.4 74.8 88.0 115 143 170
I
VLT, MAX
(60 s) [A] (200-230 V) 50.6 65.3 82.3 96.8 127 158 187
I
VLT,N
[A] (240 V) 46.0 59.4 74.8 88.0 104 130 154
I
VLT, MAX
(60 s) [A] (240 V) 50.6 65.3 82.3 96.8 115 143 170
Output S
VLT,N
[kVA] (240 V) 19.1 24.7 31.1 36.6 41.0 52.0 61.0
Max. cable cross-section to motor and
DC-bus [mm
2
/AWG] copper 16/6 35/2 35/2 50/0 70/1/0 95/3/0 120/4/0
aluminium 16/6 35/2 35/2 50/0 95/3/0
5)
90/250mcm
5)
120/300mcm
5)
Min. cable cross-section to motor and
DC-bus
[mm
2
/AWG] 10/8 10/8 10/8 16/6 10/8 10/8 10/8
Max. input current (200 V) (RMS) I
L,N
[A] 46.0 59.2 74.8 88.0 101.3 126.6 149.9
Max. cable, cross-section
power [mm
2
/AWG] copper 16/6 35/2 35/2 50/0 70/1/0 95/3/0 120/4/0
aluminium 16/6 35/2 35/2 50/0 95/3/0
5)
90/250mcm
5)
120/300mcm
5)
Max. pre-fuses [A]/UL
1 )
[A] 60 80 125 125 150 200 250
Mains contactor [Danfoss type] CI 32 CI 32 CI 37 CI 45 - - -
[AC value] AC-1 AC-1 AC-1 AC-1
Efficiency
3)
0.95
Weight IP 00 [kg] - - - - 90 90 90
Weight IP 20 [kg] 23 30 30 48 101 101 101
Weight IP 54 [kg] 38 49 50 55 104 104 104
Power loss at max. load: [W] 545 783 1042 1243 1089 1361 1613
Enclosure IP 20+NEMA 1 kit, IP 54/NEMA 12