Danfoss REP24CO3 Spezifikationen Seite 69

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 84
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 68
69
Commercial compensator with •
lockable user interface
4 application cards are available•
Can be used with P20 card to •
directly control a boiler
Easy to use user interface•
Up to 4 temperature sensors can be •
connected
Can be used as a stand alone or •
master/slave controller
Built-in optimiser•
Use with VRB/VF 3-port motorised •
valvesandAMV435actuators
The ECL Comfort 200 electronic
controller is pre-programmed for a
variety of different applications. Each
application has its own card with an
overview of the end-user and installer
settings.
The ECL Comfort 200 controller has triac
outputs for motorised valve control and
2 relay outputs for pump/valve control.
It is possible to connect up to 4
Pt 1000 temperature sensors and
communication modules.
The enclosure is designed for wall and
panel mounting as well as mounting on
a DIN rail.
Electronic Temperature Controllers
ECL200 Compensator with Optimiser Function
ECL 200
Type Designation Code No.
ECL Comfort 200 Universal hardware - 230 V a.c. 087B112000
ECL Comfort 200 Universal hardware - 24 V a.c. 087B112400
ECL Comfort 200 Base part for wall mounting or DIN rail 087B114900
ECL Comfort Connector set for panel mounting 087B114800
ECL Comfort Mounting kit for DIN rail 087B114500
For sensor options see page 67.
Following applications can be realised together with ECL Comfort 200:
Card Code No. Application Type Description Controller Outputs
(Without accessories)
P16 087B466300 Constant temperature control of hot-water circuits with flow
system or storage tank built-in heating coil
1 x 3-point
1 x 2-point
P17 087B466400 Constant temperature control of hot-water circuits with storage
charging system
1 x 3-point
2 x 2-point
P20 087B466000 Weather compensated flow temperature control of boiler systems 2 x 2-point
P30 087B465300 Weather compensated flow temperature control of heating
systems with fixed return temperature limitation
1 x 3-point
1 x 2-point
Example Application - Direct Boiler Control
Seitenansicht 68
1 2 ... 64 65 66 67 68 69 70 71 72 73 74 ... 83 84

Kommentare zu diesen Handbüchern