Commercial compensator with •
lockable user interface
A wide variety of application cards •
are available
Can be used with C75 application •
card to sequence up to 8 boilers
Easy to use user interface•
Up to 6 temperature sensors can be •
connected
Can be used as a stand alone or •
master/slave controller
Built-in optimiser•
Use with VRB/VF 3-port motorised •
valvesandAMV435actuator
The ECL Comfort 300 is an electronic
temperature controller which can be
loaded with selected applications by
means of an ECL card.
The ECL Comfort 300 controller has triac
outputs for motorised valve control
and relay outputs for burner/pump/
changeover valve control.
It is possible to connect up to 6 Pt 1000
temperature sensors and optional plug-
in modules.
The enclosure is designed for wall and
panel mounting as well as for mounting
on a DIN rail.
The ECL card contains information
about application and factory settings.
Each application has its own card with
corresponding settings.
Special applications and/or settings are
possible on request.
Electronic Temperature Controllers
ECL300 Compensator with Optimiser Function
Type Designation Code No.
ECL Comfort 300 Universal hardware - 230 V a.c. 087B113000
ECL Comfort 300 Universal hardware - 24 V a.c. 087B113400
ECL Comfort 300 with ECA 83 Universal hardware - 230 V a.c. with 2 additional analog inputs
(0-10 V) and 2 analog outputs (0-10 V)
087B183900
ECL Comfort 300 with ECA 88 Universal hardware - 230 V a.c. with2 additional pulse connec-
tors for heat meter
087B113100
ECL Comfort 200/300/301 Base part for wall mounting or DIN rail 087B114900
ECL Comfort
Connector set for panel mounting 087B114800
ECL Comfort Mounting kit for DIN rail 087B114500
For sensor options see page 67.
ECL 300
Following applications can be realised together with ECL Comfort 300:
Card Code No. Application Type Description Controller Outputs
(Without accessories)
C35 087B476100 Weather compensated flow temperature control of systems
with fixed temperature limitation. Constant temperature control
of secondarily connected DHW circuits with storage tank with
built-in heating coil. Optional ON/OFF control of the DHW circuit
in connection with primarily connected storage tank with built-in
heating coil.
1 x 3-point
2 x 2-point
C60 087B475600 Weather compensated flow temperature control of heating
systems with sliding return temperature limitation for two
independent heating circuits
2 x 3-point
2 x 2-point
C62 087B480800 Weather compensated flow temperature control of heating
systems with sliding return temperature limitation for two
independent heating circuits
2 x 3-point
2 x 2-point
C75 087B482500 Multi-stage boiler controller (up to 8 boiler steps) with constant
temperature control of DHW circuits and weather compensated
flow temperature control of a mixed and an unmixed heating
circuit
1 x 3-point
4 x 2-point*
Example Application - C75 Card-Boiler sequencing and mixing valve control