RET230 HC-3 RET230 HCA-3 RET230 HCW-3
Code No. 087N780500 087N780600 087N780800
Built-in sensor
Remote sensor
Temperature Range - Heating 5-30°C
Temperature Range - Cooling 7-32°C at dead-band of 2K
Temperature Range - Cooling 9-34°C at dead-band of 4K
Selectable dead-band 2 or 4K
Changeover Temperature Cool to heat
Heat to cool
Pipe temperature >30°C
Pipe temperature <16°C
Thermal differential in on/off mode <1°C
Temperature Accuracy ±1°C
Pipe sensor for heat/cool changeover
Manual fan 3-speed selector
Thermostat off/auto & fan on selector
LCD display of set/room temperature
Heat/cool output status LED
Power on/fan output status LED
On/Off or Chrono-proportional control
Optional compressor delay timer
Fan-coil or heat-pump configuration
Reversing valve heat or cool selection
1)
Selectable Celsius or Fahrenheit scaling
Maximum ambient temperature 45°C
Power supply 230Vac,±15%,50/60Hz
Relay outputs, heat, cool & fan
3 x SPST, 3(1)A,
10-230 Vac
2 x SPST, 3(1)A,
10-230 Vac
Dimensions (mm) 110 wide x 90 high x 40 deep
Note
1) Reversing valve function is only available if set up for heat-pump operation.
Stylish modern design•
For use in 2-pipe or 4-pipe •
fan-coil systems.
Large setting dial with LCD •
temperature display
230 volt operation•
On/off or chrono-proportional •
regulation
The RET230 HC-3 and HCW-3 are heat/
cool room thermostats designed for
2-pipe or 4-pipe fan-coil systems. These
thermostats feature an analogue setting
dial, scaled 1 to 5, a small LCD display
which normally displays actual room
temperature, but changes momentarily
to show the set temperature when the
setting dial is moved.
In addition to the heating and cooling
outputs, the thermostats incorporate
a fan relay to control the operation
of a single phase 3-speed fan motor.
A manual switch on the right of
the thermostat allows the user to
manually select the required fan
speed. An additional manual switch
on the left allows the user to turn off
the thermostat and to select whether
the fan is switched on or off with
the heating/cooling output or runs
continuously. LED indicators provide
clear indication of output status.
In addition to providing conventional
on/off control, the thermostat can be
set up at time of installation to provide
chrono-proportional output. This type
of control mode provides closer control
accuracy compared to on/off control.
RET230 HC-3 and RET230 HCA-3
Designed for use in 4-pipe fan-coil unit
systems, split packaged systems and in
air to air heat-pump systems.
RET230 HCW-3
Designed for use in 2-pipe fan coil
unit systems with central changeover
between heating and cooling.